Install CO2 Fire Suppression System Under the Floor Building 605 HomeInstall CO2 Fire Suppression System Under the Floor Building 605

Install CO2 Fire Suppression System Under the Floor Building 605

Federal Construction Group was tasked to achieve a three (3) minute soak time on the Low Pressure Bulk CO2 system installed in building 605 at SSC Pt. Loma.  This involved providing a NFS-320 Fire Alarm Control Panel with one loop control module.  Installing the monitor modules, relay modules, control modules to complete the programming for the required soak time.  For the signal release on the NFS-320 FACP, a MR-201 relay in the Electro-pneumatic relay cabinet was installed to replace the MR-101.  We provided a monitor module on the dry contact side of the MR-201 to signal the NFS-320 to send a signal to the Fike Panel for discharge.  We also provided  control modules that would interrupt the current circuitry to control the solenoid.  We extended all wiring and conduit from the Fike Panels over to the new FACP, did minor patch and repair as required and then re-tested and finalized the system.