Federal Construction Group, Inc. is tasked to prepare Room 34 of Building 31598 for the installation of customer provided Virtual Simulation Equipment for Integration and Interoperability (I&I) Equipment.

SCOPE OF WORK:
Remove existing 225KVA 120/208V transformer and replace with a new 750KVA 120/208V transformer. Reuse existing slab and connect secondary to new 2000A
Switchboard. Remove existing 800A 120/208V switchboard and replace with a new 2000A switchboard. Provide new 400A panelboard in Room 2A. Room 2A is a high
security vault; provide required seal for SCIF level security. Provide 6” PVC for cable pass-through from Section 2A into Section 2. Walls of Section 2A consist of
approximately 8”-10” masonry and/or rebar reinforced concrete with expanded metal sheeting. Provide 2 new 100A circuits for future use. Provide 2 new 20A 120V
receptacles in Room 1. Provide 10 new 30A 208V NEMA L14-30 receptacles in Room 2A. Provide 2 new 20A 120V receptacles in Room 35. Provide 2 stub ups with (2) 24”
x 24” x 16” junction boxes for future equipment southwest of transformer pad.